FR-A820-55K-90K Biến Tần Mitsubishi 55kW-90kW, 3 Pha 220 VAC: FR-A820
- FR-A820-03160(55K)
- FR-A820-03800(75K)
- FR-A820-04750(90K)
Model FR-A820-[ ](-E)(GF) | 03160 | 03800 | 04750 | |||
55K | 75K | 90K | ||||
Applicable motor capacity (kW) *1 | SLD | 75 | 90/110 | 132 | ||
LD | 75 | 90 | 110 | |||
ND (initial setting) | 55 | 75 | 90 | |||
HD | 45 | 55 | 75 | |||
Output | Rated capacity (kVA) *3 |
SLD | 120 | 145 | 181 | |
LD | 110 | 132 | 165 | |||
ND (initial setting) | 82 | 110 | 132 | |||
HD | 67 | 82 | 110 | |||
Rated current (A) |
SLD | 316 | 380 | 475 | ||
LD | 288 | 346 | 432 | |||
ND (initial setting) | 215 | 288 | 346 | |||
HD | 175 | 215 | 288 | |||
Overload current rating *4 |
SLD | 110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature of 40°C | ||||
LD | 120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C | |||||
ND (initial setting) | 150% 60 s, 200% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C | |||||
HD | 200% 60 s, 250% 3 s (inverse-time characteristics) at surrounding air temperature of 50°C | |||||
Rated voltage *5 | Three-phase 200 to 240 V | |||||
Regenerative braking | Brake transistor | FR-BU2 (Option) | ||||
Maximum brake torque *7 | 20% torque/continuous | 10% torque/ continuous |
||||
FR-ABR (when the option is used) |
― | ― | ― | |||
Power supply | Rated input AC voltage/frequency |
Three-phase 200 to 240 V 50 Hz/60 Hz | ||||
Permissible AC voltage fluctuation | 170 to 264 V 50 Hz/60 Hz | |||||
Permissible frequency fluctuation | ±5% | |||||
Rated input current (A) *8 | Without DC reactor |
SLD | ― | ― | ― | |
LD | ― | ― | ― | |||
ND (initial setting) |
266 | ― | ― | |||
HD | 216 | ― | ― | |||
With DC reactor |
SLD | 316 | 380 | 475 | ||
LD | 288 | 346 | 432 | |||
ND (initial setting) |
215 | 288 | 346 | |||
HD | 175 | 215 | 288 | |||
Power supply capacity (kVA) *9 |
Without DC reactor |
SLD | ― | ― | ― | |
LD | ― | ― | ― | |||
ND (initial setting) |
101 | ― | ― | |||
HD | 82 | ― | ― | |||
With DC reactor |
SLD | 120 | 145 | 181 | ||
LD | 110 | 132 | 165 | |||
ND (initial setting) |
82 | 110 | 132 | |||
HD | 67 | 82 | 110 | |||
Protective structure (IEC 60529) *10 | Open type (IP00) | |||||
Cooling system | Forced air cooling | |||||
Approx. mass (kg) | 54 | 74 | 74 |
=======================